Notifier FRM-1 FlashScan Relay Module

Specifications
- Manufacturer
- Notifier
- Part number
- FRM-1
- Product type
- Relay Modules
- Protocol
- FlashScan
- Platform
- FlashScan
- System type
- Addressable
- Voltage
- 24 V
- Certification
- UL Listed
Before you order
Match the part number to the one specified for your system, and check compatibility and required accessories (such as the detector base) in the manufacturer's documentation.
Product details
FRM-1 is an addressable relay module for Notifier intelligent fire alarm panels. It gives the panel two Form-C dry contacts on the SLC loop, used for jobs such as fan or damper control, door holder release and air-handler shutdown. The contacts switch on command from the panel and can be programmed to follow system events.
Key features
- Two isolated Form-C contact sets that switch together (DPDT)
- Address set with built-in rotary decimal switches
- Panel-controlled LED indicator
- Can replace a CMX-2 module that was set up for Form-C operation
- Mounts on a 4 in square box or a DNR(W) duct housing
Specifications
| Operating voltage | 15 to 32 VDC |
| Max current draw | 6.5 mA (LED on) |
| Average current | 230 µA direct poll; 255 µA group poll |
| Contact rating | 3 A @ 30 VDC resistive, non-coded (other loads per datasheet table) |
| Addresses | One of 159 module addresses per SLC loop (99 on CLIP loops) |
| Dimensions | 4.5 in H x 4 in W x 1.25 in D |
| Mounting box | 4 in square, 2-1/8 in minimum depth |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
| Humidity | 10% to 93% non-condensing |
Before you order
The module does not supervise the circuits wired to its contacts. For non-power-limited wiring the CB500 barrier is required; the SMB500 box is available for surface mounting.