Notifier FDM-1 FlashScan Dual Monitor Module

Specifications
- Manufacturer
- Notifier
- Part number
- FDM-1
- Product type
- Monitor Modules
- Protocol
- Addressable, FlashScan
- Voltage
- 24 V
- Certification
- UL Listed
Before you order
Match the part number to the one specified for your system, and check compatibility and required accessories (such as the detector base) in the manufacturer's documentation.
Product details
FDM-1 is a Notifier FlashScan dual monitor module that provides two independent two-wire initiating device circuits at two consecutive SLC addresses. It monitors normally open fire alarm and supervisory contacts, or normally open or normally closed security devices, which makes it handy where two devices such as a waterflow switch and a tamper switch sit side by side. It is intended for Notifier intelligent two-wire systems.
Key features
- Two independent Class B (Style B) input circuits in one module
- Automatically takes two consecutive addresses from a single setting
- Monitors NO fire/supervisory contacts and NO or NC security devices
- Single panel-controlled LED
- Mounts in a standard 4 in square box
Specifications
| Device type | Addressable dual monitor module |
| Inputs | 2 IDCs, Class B (Style B) only |
| Addressing | Two consecutive addresses; ones digit 0, 2, 4, 6 or 8 |
| Operating voltage | 15–32 VDC |
| Max. current draw | 6.4 mA (LED on) |
| Average current | 750 µA (LED flashing) |
| Max. IDC wiring resistance | 1,500 ohms |
| Max. IDC voltage / current | 11 V / 240 µA |
| EOL resistor | 47K ohms |
| Temperature range | 32–120°F (0–49°C) |
| Humidity | 10–93% non-condensing |
| Dimensions | 4.5 in H × 4 in W × 1.25 in D |
| Mounting | 4 in square × 2⅛ in deep box |
Before you order
Class A (Style D) input wiring is not supported; use FMM-1 modules if Class A is required. Set the address on an even number, since the module also uses the next address up; the SMB500 surface box is optional.