System Sensor MOD2W i3 Series 2-Wire Loop Test / Maintenance Module

Specifications
- Manufacturer
- System Sensor
- Part number
- MOD2W
- Product type
- Accessories
Before you order
Match the part number to the one specified for your system, and check compatibility and required accessories (such as the detector base) in the manufacturer's documentation.
Product details
The MOD2W lets a 4-wire conventional control panel take advantage of the maintenance signals from 2-wire i3 smoke detectors. It reads each detector's need-for-maintenance and freeze-trouble signals and reports them through dedicated relays, with a separate alarm relay and a loop fault relay. EZ Walk test mode lets one technician check the loop wiring and detectors.
- Supports up to 12 two-wire i3 detectors (2W-B, 2WT-B, one 2WTR-B)
- Power: 8.5 to 35 VDC; 20 mA standby @ 24 V
- Relay contacts: 100 mA @ 36 VDC resistive
- Class B (Style B) or Class A (Style D) detector loop
- Operating temperature: 32 F to 122 F; 6.04 x 6.04 x 1.16 in