Edwards
Edwards SIGA-HRD Signature Series Fixed Temperature/Rate-of-Rise Heat Detector
$58.00
$58.00
/
Shipping calculated at checkout.
Free 30-Day Returns
30 UNITS IN STOCK - FAST SHIPPING
SIGA-HRD is an Edwards Signature Series intelligent heat detector that combines a 135°F (57°C) fixed-temperature alarm point with a 15°F per minute rate-of-rise alarm point. The rate-of-rise function responds to fast, flaming fires and the fixed-temperature function responds when the air near the detector exceeds the alarm point. It is compatible only with the Signature Loop Controller and plugs into a separately ordered Signature Series detector base.
Specifications
| Detection method | Fixed temperature and rate-of-rise (thermistor) |
| Fixed temperature rating | 135°F (57.2°C); actual alarm point 129°F to 141°F (53.9°C to 60.6°C) |
| Rate-of-rise rating | 15°F per minute |
| Maximum spacing | 50 ft (15.2 m) centers |
| Operating voltage | 15.20 to 19.95 VDC |
| Normal operating current | 51 µA |
| Alarm current | 68 µA |
| Operating environment | 32°F to 100°F (0°C to 38°C), 0-93% RH noncondensing |
| Storage temperature | -4°F to 140°F (-20°C to 60°C) |
| Vibration level | 10 to 35 Hz, amplitude 0.01 in |
| Construction | High-impact engineering polymer, white |
| Status LED | Bicolor (green/red) |
| Compatible detector testers | Testifire 1000, Testifire 2000 |
| Agency listings | UL 521; CAN/ULC-S530 |
Compatibility and installation notes
- Compatible only with the Edwards Signature Loop Controller; feature support depends on the control panel.
- Compatible bases: SIGA-SB, SIGA-SB4, SIGA-RB, SIGA-RB4, SIGA-IB, SIGA-IB4, SIGA-AB4G, SIGA-AB4GT and SIGA-AB4G-LF. SIGA-LED remote LED works with SIGA-SB/SB4 only.
- Bases mount to North American 1-gang boxes, 3-1/2 in or 4 in octagon boxes 1-1/2 in (38 mm) deep; 4 in bases also fit 4 in square boxes.
- Bases accept 18 to 12 AWG wire; 16 and 18 AWG are preferred.
- The manufacturer states that heat detectors alone do not provide life safety protection; use with smoke detectors as part of a complete system.
- The detector does not sense fires where heat cannot reach it, such as inside walls or behind closed doors.
Related models
- SIGA-HFD: Signature Series 135°F fixed-temperature heat detector without rate-of-rise
- SIGA-HRD-NL: SIGA-HRD with no visible logo
- SIGA-HCD: Signature Series rate-of-rise/fixed heat and CO detector
Documents
Specifications from Edwards data sheet E85001-0647, Issue 2.4 (10-16-25). Manufacturer specifications are subject to change.