SIGA-HRD is an Edwards Signature Series intelligent heat detector that combines a 135°F (57°C) fixed-temperature alarm point with a 15°F per minute rate-of-rise alarm point. The rate-of-rise function responds to fast, flaming fires and the fixed-temperature function responds when the air near the detector exceeds the alarm point. It is compatible only with the Signature Loop Controller and plugs into a separately ordered Signature Series detector base.

Specifications

Detection method Fixed temperature and rate-of-rise (thermistor)
Fixed temperature rating 135°F (57.2°C); actual alarm point 129°F to 141°F (53.9°C to 60.6°C)
Rate-of-rise rating 15°F per minute
Maximum spacing 50 ft (15.2 m) centers
Operating voltage 15.20 to 19.95 VDC
Normal operating current 51 µA
Alarm current 68 µA
Operating environment 32°F to 100°F (0°C to 38°C), 0-93% RH noncondensing
Storage temperature -4°F to 140°F (-20°C to 60°C)
Vibration level 10 to 35 Hz, amplitude 0.01 in
Construction High-impact engineering polymer, white
Status LED Bicolor (green/red)
Compatible detector testers Testifire 1000, Testifire 2000
Agency listings UL 521; CAN/ULC-S530

Compatibility and installation notes

  • Compatible only with the Edwards Signature Loop Controller; feature support depends on the control panel.
  • Compatible bases: SIGA-SB, SIGA-SB4, SIGA-RB, SIGA-RB4, SIGA-IB, SIGA-IB4, SIGA-AB4G, SIGA-AB4GT and SIGA-AB4G-LF. SIGA-LED remote LED works with SIGA-SB/SB4 only.
  • Bases mount to North American 1-gang boxes, 3-1/2 in or 4 in octagon boxes 1-1/2 in (38 mm) deep; 4 in bases also fit 4 in square boxes.
  • Bases accept 18 to 12 AWG wire; 16 and 18 AWG are preferred.
  • The manufacturer states that heat detectors alone do not provide life safety protection; use with smoke detectors as part of a complete system.
  • The detector does not sense fires where heat cannot reach it, such as inside walls or behind closed doors.

Related models

  • SIGA-HFD: Signature Series 135°F fixed-temperature heat detector without rate-of-rise
  • SIGA-HRD-NL: SIGA-HRD with no visible logo
  • SIGA-HCD: Signature Series rate-of-rise/fixed heat and CO detector

Documents

Specifications from Edwards data sheet E85001-0647, Issue 2.4 (10-16-25). Manufacturer specifications are subject to change.